TECHNICAL DATA

FLOOR CLASSFICATION

 
PROPERTIES
 TEST RESULTS
CLASSFICATION
EN 685 / EN 649
CLASS 34 ± 43
NFPA LIFE SAFETY CODE 101
CLASS I INTERIOR FLOOR FINISH
STANDARD SPECIFICATION FOR SOLD VINYL FLOOR TILE 
ASTM F 1700-99
PASSED
FULFILS PRODUCT REQUIREMENT
EN 649 / SS-T-312B
 PASSED
 OUTGASSING : CVCM
ASTM E 594
 LOW EMISSION  CVCM 2.65 %

PHYSICAL FEATURES

Click to edit table header
 
 
THICKNESS / EN 428 
ASTM F 386
  2MM / 3MM
 
SIZE / EN 427
ASTM F 386
  610 X 610 (MM)
 
WEIGHT / M2
EN 430
2MM : 3.62KG / M2
3MM : 5.43KG / M2
 
FLEXIBILITY
LEXIBILITY
ASTM F 137
 0.1%
<0.30%
 
FLEXIBILITY
ASTM F 137
NO CRACK
 
SQUARENESS
ASTM F 540
± 0.30
 
RESIDUAL INDENTATION (150MIN)
EN 433 / DIN 51955
ASTM F 142
2.0MM - 0.03MM / 3.0MM - 0.04MM
ABRASION RESISTANCE
ASTM D 1044
(CS-10-F-WHEEL, 500GM WEIGHT)
ASTM D 4060
(CS-10-F-WHEEL, 1,000G, 1,000 CYCLES)

CYCLES 
2,500
5,000
7,500
10,000

<97MG
0.48% GAUGE LOSS
0.95
1.41
1.87
HARDNESS (SHORE D)
ASTM D 2240
  <85
 
EFFECT TO CASTOR CHAIR
EN 425
 NO DAMAGE

ELECTRIC FEATURES

Click to edit table header
 
ANSI / ESD S7.1 - 2005
ASTM F 150 / NFPA 99
UL 779 (LISTED NO. 22L9)
  2.5 X  10⁴ < R < 10⁶  Ω
ELECTROSTATIC PROPENSITY / STATIC GENERATION
AATCC 134
< 50 V
STATIC DECAY
FEDERAL TEST METHOD 10IC, M4046) : 500v TO ZERO
MIL B 81705C (5kV DECAY TIME / SEC)
  < 00.01 SEC

RESISTANCE TO CHEMICAL

Click to edit table header
 
CHEMICAL RESISTANCE
EN 423 / DIN 51958
ASTM D 543 / ASTM F 925
EXCELLENT

FIRE RESISTANCE

Click to edit table header
 
FIRE RESISTANCE 
DIN 4102 / B 3810 / B 3800
SOMKE DENSITY : ASTM E 622 / NFPA 258
CRITICAL RADIANT FLUX : ASTM 3 648 / NFPA 253 / DIN 51960
FLAE SPREAD : AST E 84 / NFPA 225
 INFLAMABLE , HARD TO IGNITE
CLASS 1 ( < 450)
CLASS 1 ( > 1.8W / M2)
< 75

MISCELLANEOUS FEATURES

Click to edit table header
 
COLOR FASTNESS
ISO 105 B 02 / MET.3 - DIN 53389
 5 - 6
EASE OF DECONTAMINATION
DIN 25415 - 1 / ISO 8690
 EXCELLENT
WATERPROOF
ASTM D 570, WATER ABSORPTION OF PLASTICS
 < 0.15 %
 WATERPROOF
ASTM D 570, WATER ABSORPTION OF PLASTICS
 YES
 RECYCLABLE
 YES
TOXIC FUMES FROM BRUNING
BS 6853 : 1999 ANNEX B, 
B.1 MASS BASED TEST METHOD NF X 70-100(2006) 
PASSED
 